Security-Constrained Unit Commitment (SCUC) Model

Overview

This project implements a Security-Constrained Unit Commitment (SCUC) model for the IEEE 73-bus system using AMPL. The model optimizes generator scheduling while ensuring system reliability under transmission constraints, generator contingencies, renewable variability, and transmission contingencies. It employs a Benders decomposition approach to iteratively solve subproblems and enforce security constraints.

Features

  • Optimizes generator commitment and dispatch for a 24-hour horizon.
  • Handles generator and transmission contingencies.
  • Incorporates renewable scenario variability using wind data.
  • Uses Power Transfer Distribution Factors (PTDF) and Line Outage Distribution Factors (LODF) for power flow calculations.
  • Implements Benders cuts to achieve convergence across subproblems.

Project Structure

The repository contains the following files:

  • Model Files:
    • ieee73_scuc_main.mod: Main SCUC model defining base case optimization.
    • scuc_gc_sub.mod: Subproblem for generator contingencies.
    • scuc_rs_sub.mod: Subproblem for renewable scenarios.
    • scuc_rs_gc_sub.mod: Subproblem for renewable scenarios with generator contingencies.
    • scuc_rs_tc_sub.mod: Subproblem for renewable scenarios with transmission contingencies.
  • Data Files:
    • ieee73_sced_bus.dat: Bus data (bus numbers, power demand).
    • ieee73_sced_gen.dat: Generator data (operational parameters, costs).
    • ieee73_sced_branch.dat: Branch data (from/to buses, reactance, thermal ratings).
    • ieee73_scuc_load_deviation24.dat: Load deviation data (max/min deviations).
    • ptdf_ieee73.dat: PTDF matrix for power flow calculations.
    • winds.dat: Wind scenario data.
    • ieee73_scuc_baseload24.dat: Base load data for 24-hour periods.
  • Supporting Files:
    • requirements.txt: Lists dependencies (AMPL, Gurobi).

Prerequisites

  • AMPL: Install AMPL from ampl.com. Ensure it is added to your system PATH.
  • Gurobi Solver: Install Gurobi from gurobi.com with a valid license. Configure the AMPL-Gurobi interface as per AMPL's Gurobi instructions.
  • Data Files: Ensure all .dat files listed above are present in the working directory.

Installation

  1. Clone the Repository:
    git clone https://github.com/your-username/scuc-model.git
    cd scuc-model
  2. Install AMPL and Gurobi:
    • Follow installation instructions for AMPL and Gurobi from their respective websites.
    • Verify AMPL can access Gurobi by running:
      ampl -v
  3. Prepare Data Files:
    • Place all .dat files in the same directory as the .mod files.
    • Ensure data files are correctly formatted to match the model’s parameter definitions.

Usage

  1. Run the Model:

    • Open AMPL in the project directory.
    • Load and solve the main model:
      model ieee73_scuc_main.mod;
      solve;
    • The model iteratively solves subproblems, adding Benders cuts until convergence.
  2. Outputs:

    • Console: Displays total solve time, cut counts (generator, renewable, transmission contingencies), total cost, and spinning reserve allocations.
    • Log File: Infeasibility details are logged to file.log.
    • Key variables (e.g., gen_supply, line_flow, spin) can be displayed using AMPL’s display command.
  3. Example Commands:

    display COST;                    # Total cost
    display n_cut_GC, n_cut_RS, n_cut_RSGC, n_cut_RSTC;  # Cut counts
    display sum{t in LOAD, g in GEND} spin[t,g];         # Total spinning reserve

Model Details

  • Objective: Minimize total cost, including generation, startup, no-load, and spinning reserve costs.
  • Constraints:
    • Unit commitment (startup, minimum up/down times).
    • Generation bounds and ramping limits.
    • Supply-demand balance and DC power flow.
    • Transmission constraints using PTDF and LODF.
    • Contingency handling for generators, transmission lines, and renewable scenarios.
  • Subproblems:
    • Generator contingency: Ensures feasibility post-generator outages.
    • Renewable scenario: Accounts for wind variability.
    • Renewable with generator contingency: Combines renewable variability and generator outages.
    • Renewable with transmission contingency: Combines renewable variability and line outages.
  • Convergence: Iterates up to 10 times, adding cuts until no new violations occur.

Notes

  • The model assumes a 24-hour horizon with hourly load and generation data.
  • Radial lines (branches 51 and 88) are excluded from certain LODF calculations.
  • Gurobi solver options include show_stats and suppressed messages for subproblems.
  • Regulation reserve constraints are commented out and not active.

Limitations

  • Piecewise linear cost segments are not optimized for compactness.
  • Data file consistency is critical to avoid infeasibility.
  • The model assumes all generators and buses are defined in the provided .dat files.

Troubleshooting

  • Infeasibility Errors: Check file.log for details on infeasible subproblems (time period, contingency type).
  • Data Issues: Verify .dat file formats and consistency with model parameters.
  • Solver Errors: Ensure Gurobi is licensed and correctly linked to AMPL.
  • Convergence Issues: If the model does not converge, check for data inconsistencies or increase MAX_ITER (default: 10).